Actual signals and parameters 149
9907
MOTOR NOM FREQ
10.0 … 500 Hz
0.1 Hz
60 Hz (US)
Defines the nominal motor frequency.
• Range: 10 … 500 Hz (typically 50 or 60 Hz)
• Sets the frequency at which output voltage equals parameter
• Field weakening point = Norm freq * Supply Volt / Mot Nom Volt
9908
MOTOR NOM
SPEED
50 … 30000 rpm
1 rpm
Size
dependent
Defines the nominal motor speed.
• Must equal the value on the motor rating plate.
9909
MOTOR NOM
POWER
0.15 … 1.5*P
N
0.1 Hp
0.2 HP (US)
Defines the nominal motor power.
• Must equal the value on the motor rating plate.
9914
PHASE INVERSION
NO
Inverts two phases in the motor cable. This changes the direction of the motor rotation
without having to exchange the positions of two motor cable phase conductors at the
drive output terminals or at the motor connection box.
• NO – Phases not inverted.
• YES – Phases inverted.
Group 99: Start-up data
Code Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...