![ABB ACS320 series User Manual Download Page 393](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965393.webp)
Technical data 393
Losses, cooling data and noise
Losses and cooling data
Frame size R0 has natural convection cooling. Frame sizes R1…R4 are provided
with an internal fan. The air flow direction is from bottom to top.
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O and panel not in use) and maximum load
(all digital inputs in the on state and the panel, fieldbus and fan in use). The total heat
dissipation is the sum of the heat dissipation in the main and control circuits.
Type Code
Heat dissipation
Air flow
Main circuit
Control circuit
Rated current
Min
Max
W
BTU/Hr
W
BTU/Hr
W
BTU/Hr
m
3
/h
ft
3
/min
1-phase supply voltage 200 - 240 V units
ACS320-01U-02A4-2
19
65
6.1
21
22.7
78
-
-
ACS320-01U-04A7-2
38
130
9.5
32
26.4
90
24
14
ACS320-01U-06A7-2
60
205
9.5
32
26.4
90
24
14
ACS320-01U-07A5-2
62
212
10.5
36
27.5
94
21
12
ACS320-01U-09A8-2
83
283
10.5
36
27.5
94
21
12
3-phase supply voltage 200 - 240 V units
ACS320-03U-02A6-2
19
65
6.1
21
22.7
78
-
-
ACS320-03U-03A9-2
31
106
6.1
21
22.7
78
-
-
ACS320-03U-05A2-2
38
130
9.5
32
26.4
90
24
14
ACS320-03U-07A4-2
60
205
9.5
32
26.4
90
24
14
ACS320-03U-08A3-2
62
212
9.5
32
26.4
90
21
12
ACS320-03U-10A8-2
83
283
10.5
36
27.5
94
21
12
ACS320-03U-14A6-2
112
383
10.5
36
27.5
94
52
31
ACS320-03U-19A4-2
152
519
10.5
36
27.5
94
52
31
ACS320-03U-26A8-2
250
854
16.6
57
35.4
121
71
42
ACS320-03U-34A1-2
270
922
33.4
114
57.8
197
96
57
ACS320-03U-50A8-2
430
1469
33.4
114
57.8
197
96
57
3-phase supply voltage 380 - 480 V units
ACS320-03U-01A2-4
11
38
6.6
23
24.4
83
-
-
ACS320-03U-01A9-4
16
55
6.6
23
24.4
83
-
-
ACS320-03U-02A4-4
21
72
9.8
33
28.7
98
13
8
ACS320-03U-03A3-4
31
106
9.8
33
28.7
98
13
8
ACS320-03U-04A1-4
40
137
9.8
33
28.7
98
13
8
ACS320-03U-05A6-4
61
208
9.8
33
28.7
98
19
11
ACS320-03U-07A3-4
74
253
14.1
48
32.7
112
24
14
ACS320-03U-08A8-4
94
321
14.1
48
32.7
112
24
14
ACS320-03U-12A5-4
130
444
12.0
41
31.2
107
52
31
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...