322 Fieldbus control
48
RESET RUN
TIME
Commanded by FLN to reset the cumulative run timer (1
= RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any
need for an explicit command to clear the point before a
subsequent reset can be issued.
49
RESET KWH
Commanded by FLN to reset the cumulative kilowatt-
hour counter (1 = RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any
need for an explicit command to clear the point before a
subsequent reset can be issued.
50
PRC PID GAIN
Sets the proportional gain of the active Process PID set,
as selected by Point 54, PRC PID SEL (1 = SET2, 0 =
SET1).
4001 (SET1)
4101 (SET2)
51
PRC PID ITIM
Sets the integration time of the active Process PID set,
as selected by Point 54, PRC PID SEL (1 = SET2, 0 =
SET1).
4002 (SET1)
4102 (SET2)
52
PRC PID DTIM
Sets the derivation time of the active Process PID set,
as selected by Point 54, PRC PID SEL (1 = SET2, 0 =
SET1).
4001 (SET1)
4101 (SET2)
53
PRC PID DFIL
Sets the time constant for the error-derivative of the
active Process PID set, as selected by Point 54, PRC
PID SEL
(1 = SET2, 0 = SET1).
4004 (SET1)
4104 (SET2)
54
PRC PID SEL
Selects the active Process PID set (1 = SET2, 0 =
SET1).
4027
55
EXT PID GAIN
Sets the proportional gain of the External PID controller. 4201
56
EXT PID ITIM
Sets the integration time of the External PID controller. 4202
57
EXT PID DTIM
Sets the derivation time of the External PID controller.
4203
58
EXT PID DFIL
Sets the time constant for the error-derivative of the
External PID controller.
4204
59
LOCK PANEL
Command by FLN to lock the panel and prevent
parameter changes (1 = LOCK, 0 = UNLOCK).
1602
60
INPUT REF 1
Sets Input Reference 1.
Parameter 1102 must be set to COMM for FLN to control
this value.
61
INPUT REF 2
Sets Input Reference 2.
Parameter 1106 must be set to COMM for FLN to control
this value.
62
EXT PID STPT
The setpoint for the External PID controller.
The function of this point requires parameter 4210, PID
Setpoint Select, to be set to 19 (Internal).
4211
63
EXT PID FBCK
The External PID feedback signal.
0131
64
EXT PID DEV
The deviation of the External PID output signal from its
setpoint.
0133
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...