208 Actual signals and parameters
Group 31: Automatic reset
This group defines conditions for automatic resets. An automatic reset occurs after a
particular fault is detected. The drive holds for a set delay time, then automatically
restarts. You can limit the number of resets in a specified time period, and you can set
up automatic resets for a variety of faults.
3023
WIRING FAULT
0, 1
1
1
Selects how the drive reacts when incorrect input power and motor cable connection
is detected (ie, the input power cable is connected to the motor connection of the
drive).
0 = DISABLE – No action.
1 = ENABLE – The drive trips on fault
3027
OPTION COM LOSS
0, 1
1
1
Selects how the drive reacts when the MREL-01 output relay module is removed from
the drive, and parameters
have non-zero values.
0 = DISABLE – Prevents the fault 1006 PAR EXT RO even when MREL-01 is
disconnected.
1 = ENABLE – MREL-01 is constantly monitored for disconnection. The drive trips on
fault 1006 PAR EXT RO if external relay outputs are configured for use.
Group 31: Automatic reset
Code
Description
Range
Resolution
Default
S
3101
NUMBER OF
TRIALS
0…5
1
5
Sets the number of allowed automatic resets within a trial period defined by parameter
• If the number of automatic resets
exceeds this limit (within the trial
time), the drive prevents additional
automatic resets and remains
stopped.
• Starting then requires a successful
reset performed from the control panel or from a source selected by parameter
Example:
Three faults have occurred in the trial time. The last is reset only if the value
for parameter
is 3 or more.
3102
TRIAL TIME
1.0 … 600.0 s
0.1 s
30.0 s
Sets the time period used for counting and limiting the number of resets.
• See parameter
.
3103
DELAY TIME
0.0 … 120.0 s
0.1 s
0.0 s
Sets the delay time between a fault detection and attempted drive restart.
• If DELAY TIME = zero, the drive resets immediately.
Group 30: Fault functions
Code
Description
Range
Resolution
Default
S
X
X X
Time
Trial time
x = Automatic reset
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...