![ABB ACS320 series User Manual Download Page 148](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965148.webp)
148 Actual signals and parameters
Parameter listing
Parameter data is specific to ACS320 firmware version 4.01C.
Group 99: Start-up data
This group defines special Start-up data required to:
• set up the drive
• enter motor information.
Note:
Parameters checked under the heading “S” can be modified only when the
drive is stopped.
Group 99: Start-up data
Code Description
Range
Resolution
Default
S
9901
LANGUAGE
0...25
1
0
Selects the display language.
9902
APPLIC MACRO
-3...21
1
1
Selects an application macro. Application macros automatically edit parameters to
configure the ACS320 for a particular application. See
for
application macro descriptions.
9905
MOTOR NOM VOLT
115 … 345 V (200 V, US)
230 … 690 V (400 V, US)
288 … 862 V (600 V, US)
1 V
1 V
1 V
230 V
460 V
575 V
Defines the nominal motor voltage.
• Must equal the value on the motor rating
plate.
• Sets the maximum drive output voltage
supplied to the motor.
• Drive cannot supply the motor with a
voltage greater than the mains voltage.
9906
MOTOR NOM CURR
0.15*I
2N
… 1.5*I
2N
0.1 A
1.5*I
2N
Defines the nominal motor current.
• Must equal the value on the motor rating plate.
0= ENGLISH
1= ENGLISH (AM)
2= DEUTSCH
3= ITALIANO
4= ESPAÑOL
5= PORTUGUES
6= NEDERLANDS
7= FRANCAIS
8= DANSK
9= SUOMI
10= SVENSKA
11= RUSSKI
12= POLSKI
13= TÜRKCE
14= CZECH
15= MAGYAR
16= ELLINIKA
17= CHINESE
18= KOREAN
19= JAPANESE
1= HVAC DEFAULT 2= SUPPLY FAN
3= RETURN FAN
4= CLNG TWR FAN
5= CONDENSER
6= BOOSTER PUMP 7= PUMP ALTERNA 8= INT TIMER
9= INT TIMER CS
10= FLOATING PNT
11= DUAL SETPPID 12= DL SP PID CS
13= E -BYPASS
14= HAND CONTROL 15= E-CLIPSE
21= AC500 MODBUS
Output voltage
Output
9907
frequency
9905
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...