Fault tracing 369
0009
MOT OVERTEMP
(4310)
bit 8
(programmable fault
function
Motor temperature is
too high (or appears to
be too high) due to
excessive load,
insufficient motor
power, inadequate
cooling or incorrect
start-up data.
Check motor ratings, load and cooling.
Check start-up data.
Check fault function parameters.
Measured motor
temperature has
exceeded fault limit set
by parameter
Check value of fault limit.
Check that actual number of sensors
corresponds to value set by parameter
.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan,
clean cooling surfaces, etc.
0010
PANEL LOSS
(5300)
bit 9
(programmable fault
function
Control panel selected
as active control
location for drive has
ceased
communicating.
Check panel connection.
Check fault function parameters.
Check control panel connector.
Refit control panel in mounting
platform.
If drive is in external control mode
(REM) and is set to accept start/stop,
direction commands or references via
control panel:
Check
and
settings.
0012
MOTOR STALL
(7121)
bit 11
(programmable fault
function
Motor is operating in
stall region due to eg
excessive load or
insufficient motor
power.
Check motor load and drive ratings.
Check fault function parameters.
0014
EXT FAULT 1
(9000)
bit 13
(programmable
External fault 1
Check external devices for faults.
Check parameter
setting.
0015
EXT FAULT 2
(9001)
bit 14
(programmable
External fault 2
Check external devices for faults.
Check parameter
setting.
0016
EARTH FAULT
(2330)
bit 15
(programmable fault
function
Drive has detected a
ground fault in motor
or motor cable.
Check motor.
Check fault function parameters.
Check motor cable. Motor cable length
must not exceed maximum
specifications. See section
on page
.
CODE FAULT
CAUSE
WHAT TO DO
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...