Actual signals and parameters 163
Group 11: Reference select
Code
Description
Range
Resolution
Default
S
1101
KEYPAD REF SEL
1,2
1
1
Selects the reference controlled in local control mode.
1 = REF1 (Hz/rpm) – Frequency reference in Hz.
2 = REF2 (%) – %-reference.
1102
EXT1/EXT2 SEL
-5...12
1
0
Defines the source for selecting between the two external control locations EXT1 or
EXT2. Thus, defines the source for Start/Stop/Direction commands and reference
signals.
0 = EXT1 – Selects external control location 1 (EXT1).
for EXT1’s Start/Stop/Dir definitions.
for EXT1’s reference definitions.
1 = DI1 – Assigns control to EXT1 or EXT2 based on the state of DI1
(DI1 activated = EXT2; DI1 de-activated = EXT1).
2…5 = DI2…DI5 – Assigns control to EXT1 or EXT2 based on the state of the
selected digital input. See DI1 above.
7 = EXT2 – Selects external control location 2 (EXT2).
for EXT2’s Start/Stop/Dir definitions.
for EXT2’s reference definitions.
8 = COMM – Assigns control of the drive via external control location EXT1 or EXT2
based on the fieldbus control word.
• Bit 5 of the Command word 1 (parameter
) defines the
active external control location (EXT1 or EXT2).
• See Fieldbus user’s manual for detailed instructions.
9 = TIMER 1 – Assigns control to EXT1 or EXT2 based on the state of the Timer
(Timer activated = EXT2; Timer de-activated = EXT1. See
10…12 = TIMER 2… 4 – Assigns control to EXT1 or EXT2 based on the state of the
Timer. See TIMER 1 above.
-1 = DI1(INV) – Assigns control to EXT1 or EXT2 based on the state of DI1
(DI1 activated = EXT1; DI1 de-activated = EXT2).
-2…-5 = DI2(INV)…DI5(INV) – Assigns control to EXT1 or EXT2 based on the state of
the selected digital input. See DI1(INV) above.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...