218 Actual signals and parameters
Group 36: Timed functions
This group defines the timed functions. The timed functions include:
• four daily start and stop times
• four weekly start, stop and boost times
• four timers for collecting selected periods together.
A timer can be connected to multiple time periods and a time period can be in multiple
timers.
3502
INPUT SELECTION
1…7
1
1
Selects the source for the motor temperature measurement signal.
1 = AI1 – Analog input AI1. Used when Pt100 or PTC sensor is selected for the
temperature measurement.
2 = AI2 – Analog input AI2. Used when Pt100 or PTC sensor is selected for the
temperature measurement.
3 = DI1 – Digital input DI1. Used when the value of parameter
set to THERM(0)/THERM(1).
4 = DI2 – Digital input DI2. Used when parameter
value is set to
THERM(0)/THERM(1).
5 = DI3 – Digital input DI3. Used when parameter
value is set to
THERM(0)/THERM(1).
6 = DI4 – Digital input DI4. Used when parameter
value is set to
THERM(0)/THERM(1).
7 = DI5 – Digital input DI5. Used when parameter
value is set to
THERM(0)/THERM(1).
3503
ALARM LIMIT
Depends on sensor
1
0
Defines the alarm limit for motor temperature measurement. Alarm
indication is given when the limit is exceeded. When parameter
value is set to THERM(0)/THERM(1): 1 = alarm.
3504
FAULT LIMIT
Depends on sensor
1
0
Defines the fault trip limit for motor temperature measurement. The drive trips on fault
when the limit is exceeded. When parameter
value is set to THERM(0)/THERM(1): 1 = fault.
3505
AO EXCITATION
0
Enables current feed from analog output AO. The parameter setting overrides the
settings in
• With PTC the output current is 1.6 mA.
• With Pt 100 the output current is 9.1 mA.
0 = DISABLE
1 = ENABLE
Group 35: Motor temp meas
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...