362 Fault tracing
2009
DEVICE
OVERTEMP
bit 8
Drive IGBT
temperature is
excessive. Alarm limit
is 120 °C.
Check ambient conditions. See also
section
on page
Check air flow and fan operation.
Check motor power against unit
power.
2010
MOTOR TEMP
bit 9
(programmable fault
function
…
Motor temperature is
too high (or appears to
be too high) due to
excessive load,
insufficient motor
power, inadequate
cooling or incorrect
start-up data.
Check motor ratings, load and
cooling.
Check start-up data.
Check fault function parameters.
Measured motor
temperature has
exceeded alarm limit
.
Check value of alarm limit.
Check that actual number of sensors
corresponds to value set by
parameter (
).
Let motor cool down. Ensure proper
motor cooling: Check cooling fan,
clean cooling surfaces, etc.
2012
MOTOR STALL
bit 11
(programmable fault
function
…
)
Motor is operating in
stall region due to, eg,
excessive load or
insufficient motor
power.
Check motor load and drive ratings.
Check fault function parameters.
2013
1)
AUTORESET
bit 12
Automatic reset alarm
Check parameter
settings.
2014
1)
AUTOCHANGE
bit 13
PFA autochange
function is active.
See parameter
.
2015
PFC I LOCK
bit 14
PFA interlocks are
active.
Drive cannot start
• any motor (when Autochange is
used)
• the speed regulated motor (when
Autochange is not used).
See parameter group
.
2018
1)
PID
SLEEP
bit 1
Sleep function has
entered sleeping
mode.
See parameter
.
2020
OVERRIDE
Override mode is
.
See sections
and
.
2021
START ENABLE 1
MISSING
bit 4
No Start Enable 1
signal received
Check parameter
settings.
Check digital input connections.
Check fieldbus communication
settings.
CODE
ALARM
CAUSE
WHAT TO DO
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...