Actual signals and parameters 279
Default values with different macros
When application macro is changed (
), the software updates
the parameter values to their default values. The table below shows the parameter
default values for different macros. For other parameters, the default values are the
same for all macros. See the parameter list starting on page
.
Index Name/
Selection
HVAC
DEFAULT
SUPPLY FAN RETURN FAN CLNG TWR
FAN
CONDENSER
BOOSTER
PUMP
PUMP
ALTERNA
1 = HVAC
DEFAULT
2 = SUPPLY
FAN
3 = RETURN
FAN
4 = CLNG
TWR FAN
5 =
CONDENSER
6 =
BOOSTER
PUMP
7 = PUMP
ALTERNA
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 = DI1
1 =
FORWARD
1 =
FORWARD
1 = FORWARD 1 =
FORWARD
1 = FORWARD
1 = FORWARD 1 = FORWARD
0 = EXT1
0 = EXT1
0 = EXT1
0 = EXT1
0 = EXT1
0 = EXT1
0 = EXT1
1 = AI1
1 = AI1
1 = AI1
1 = AI1
1 = AI1
1 = AI1
1 = AI1
19 =
PID1OUT
19 =
PID1OUT
19 = PID1OUT 19 =
PID1OUT
19 = PID1OUT 19 =
PID1OUT
19 =
PID1OUT
3 = DI3
3 = DI3
3 = DI3
3 = DI3
3 = DI3
3 = DI3
0 = NOT SEL
20.0%
20.0%
20.0%
20.0%
20.0%
20.0%
20.0%
1 = READY
7 =
STARTED
7 = STARTED 1 = READY
1 = READY
1 = READY
31 = PFA
0 = NOT SEL 2 = DI2
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL
0 = NOT SEL 0 = NOT SEL
2 = RUN
2 = RUN
2 = RUN
2 = RUN
2 = RUN
2 = RUN
2 = RUN
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL
0 = NOT SEL 0 = NOT SEL
30.0 s
30.0 s
30.0 s
30.0 s
30.0 s
10.0 s
10.0 s
30.0 s
30.0 s
30.0 s
30.0 s
30.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
10.0 s
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.0 s
3.0 s
3.0 s
3.0 s
3.0 s
3.0 s
3.0 s
4101 GAIN
2.5
2.5
2.5
2.5
2.5
2.5
2.5
4102 INTEGRATION
TIME
3.0 s
3.0 s
3.0 s
3.0 s
60.0 s
3.0 s
3.0 s
3.0 s
3.0 s
3.0 s
3.0 s
3.0 s
3.0 s
3.0 s
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0.0 =
NOT SEL
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL
0 = NOT SEL 1 = ACTIVE
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...