Actual signals and parameters 203
Group 30: Fault functions
This group defines situations that the drive should recognize as potential faults and
defines how the drive should respond if the fault is detected.
2907
USER MWh TRIG
0.0 … 6553.5 MWh
0.1 MWh
0.0
Defines the trigger point for the drive power consumption counter. Value is compared
to the value of parameter
• Megawatt hours. If parameter value is set to zero, the trigger is disabled.
0.0 = NOT SEL
2908
USER MWh ACT
0.0 … 6553.5 MWh
0.1 MWh
0.0
Defines the actual value of the drive power consumption counter. When parameter
has been set to a non zero value, the counter starts. When
the actual value of the counter exceeds the value defined by parameter
maintenance notice is displayed on the panel.
• Megawatt hours. Parameter is reset by setting it to zero.
Group 30: Fault functions
Code
Description
Range
Resolution
Default
S
3001
AI<MIN FUNCTION
0…3
1
0
Defines the drive response if the analog input (AI) signal drops below the fault limits
and is used:
• as the active reference source (
• as the Process or External PID controllers' feedback or setpoint source (
,
or
) and
the corresponding PID controller is active.
set the minimum limits.
0 = NOT SEL – No response.
1 = FAULT – Displays a fault (
) and the drive coasts
to a stop.
2 = CONST SP 7 – Displays a warning (
) and sets
speed using
3 = LAST SPEED – Displays a warning (
) and sets
speed using the last operating level. This value is the average speed over the last
10 seconds.
WARNING!
If you select CONST SP7 or LAST SPEED, make sure that continued
operation is safe when the analog input signal is lost.
Group 29: Maintenance trig
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...