![ABB ACS320 series User Manual Download Page 368](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965368.webp)
368 Fault tracing
Fault messages generated by the drive
CODE FAULT
CAUSE
WHAT TO DO
0001
OVERCURRENT
(2310)
bit 0
Output current has
exceeded trip level.
Check motor load.
Check acceleration time (
and
Check motor and motor cable
(including phasing).
Check ambient conditions. Load
capacity decreases if installation site
ambient temperature exceeds 40 °C.
See section
on page
.
0002
DC OVERVOLT
(3210)
bit 1
Excessive
intermediate circuit DC
voltage. DC
overvoltage trip limit is
420 V for 200 V drives
and 840 V for 400 V
drives.
Check that overvoltage controller is
on.
Check input power line for static or
transient overvoltage.
Check deceleration time (
).
0003
DEV OVERTEMP
(4210)
bit 2
Drive IGBT
temperature is
excessive. Fault trip
limit is 135 °C.
Check ambient conditions. See also
section
on page
Check air flow and fan operation.
Check motor power against unit
power.
0004
SHORT CIRC
(2340)
bit 3
Short circuit in motor
cable(s) or motor
Check motor and motor cable.
0006
DC UNDERVOLT
(3220)
bit 5
Intermediate circuit DC
voltage is not sufficient
due to missing input
power line phase,
blown fuse, rectifier
bridge internal fault or
too low input power.
Check that undervoltage controller is
on (parameter
Check input power supply and fuses.
0007
AI1 LOSS
(8110)
bit 6
(programmable fault
Analog input AI1 signal
has fallen below limit
defined by parameter
Check fault function parameter
settings.
Check for proper analog control signal
levels.
Check connections.
0008
AI2 LOSS
(8110)
bit 7
(programmable fault
Analog input AI2 signal
has fallen below limit
defined by parameter
Check fault function parameter
settings.
Check for proper analog control signal
levels.
Check connections.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...