background image

Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 1

TC10

LIMIT CONTROL TYPE

Engineering Manual

Code: IM 05C01E81-12EN

First edition: Nov. 2019

Yokogawa Electric Corporation

2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750 Japan

www.yokogawa.com/ns

1.  OUTLINE DIMENSIONS (mm)

1.1  INSTRUMENT DIMENSIONS

48

4

8

48

PV

AT

14

11

8 mm max.

Optional
gasket 

1.2  PANEL CUT-OUT

65 mm min.

2.56 in min.

45

+0.6

 mm

1.78

+0.023

 in

45

+0.6

 mm

1.78

+0.023

 in

65 mm mi

n.

2.56 in min.

1.3  MOUNTING REQUIREMENTS

This instrument is intended for permanent installation, for 
indoor use only, in an electrical panel which encloses the 
rear housing, exposed terminals and wiring on the back.

Select a mounting location having the following characteristics:

1. 

It should be easily accessible;

2. 

There is minimum vibrations and no impact;

3. 

There are no corrosive gases;

4. 

There are no water or other fl uids (i.e. condensation);

5. 

The ambient temperature is in accordance with the 
operative temperature (0 to 50°C);

6. 

The relative humidity is in accordance with the instrument 
specifi cations (20 to 90%);

The instrument can be mounted on panel with a maximum 
thickness of 8 mm.

            When the maximum front protection (IP65) is    

            desired, the optional gasket must be mounted.

            This is mandatory for FM approval.

2.  CONNECTION DIAGRAM

RS485

TERMINALS

Pin connector

1.4 mm max.
(0.055 in.)

Stripped wire
L:

5.5 mm
(0.21 in.)

L

ELECTRICAL CONNECTIONS

Thermo-

couple

DI1

OP3

Limiter

OP4

(note)

Output 4: 0-12V DO

Analogue input

mV, V

mA

Note:

Terminal 4 can be programmed as:

- 0 to 12 V SSR Drive Output

(OP4) connecting

the load between terminals 4 and 16;

- 12 Vdc (20 mA) transmitter power supply

connecting the 2 wire transmitter between
terminals 4 and 1; for 3 wire transmitter connect
terminal 4 to transmitter power supply input and
terminal 1 and 2 to transmitter signal output.

Neutral

Line

12VDC
(note)

PV

4 to 20 mA

3 wire transmitter

12VDC
(note)

PV

Pt100

Pt1000

100 to 240 Vac

4 to 20 mA

2 wire transmitter

OP1

Output 1: 4-20 mA

Output

2.1  GENERAL NOTES ABOUT WIRING

1. 

Do not run input wires together with power cables.

2. 

External components (like zener barriers, etc.) connected 
between sensor and input terminals may cause errors in 
measurement due to excessive and/or not balanced line 
resistance or possible leakage currents.

3. 

When a shielded cable is used, it should be connected at 
one point only.

4. 

Pay attention to the line resistance; a high line resistance 
may cause measurement errors.

2.2  INPUTS

2.2.1  Termocouple Input

1

2

+

_

External resistance:

 100

W

 max., maximum error 25 

µ

V.

Continuity detection current

: 250 nA.

Cold junction:

 automatic compensation between 0 to 55°C.

TC 10 - L

Summary of Contents for TC 10-L

Page 1: ...ust be mounted This is mandatory for FM approval 2 CONNECTION DIAGRAM RS485 TERMINALS Pin connector 1 4 mm max 0 055 in Stripped wire L 5 5 mm 0 21 in L ELECTRICAL CONNECTIONS Thermo couple DI1 OP3 Li...

Page 2: ...20 mA input wiring for passive transmitter using an external pws _ _ 1 2 0 4 to 20 mA Passive transmitter _ External PWS 0 4 to 20 mA input wiring for active transmitter 0 4 to 20 mA Active transmitte...

Page 3: ...5 VDC Logic level 1 12 V 20 20 mA max Note Overload protected 2 4 SERIAL INTERFACE D D D D D D D D RS 485 5 6 Interface type Isolated 50 V RS 485 Voltage levels According to EIA standard Protocol type...

Page 4: ...Resolution 30000 counts Total Accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance directive EMC 2004 108 CE EN 61326 1 directive LV 200...

Page 5: ...exceed SP at power on SP HYS PV A B D C EXCEEDED LAMP OUT LAMP lit off OUTPUT RELAY confirmation accepted lit off Energized De energized OFF OFF OFF Lit ON OFF Lit OFF Power ON OFF OFF ON OFF 5 3 HOW...

Page 6: ...TC J 50 1000 C 58 1832 F crAL TC K 50 1370 C 58 2498 F S TC S 50 1760 C 58 3200 F r TC R 50 1760 C 58 3200 F t TC T 70 400 C 94 752 F n TC N 50 1300 C 58 2372 F Pt1 RTD Pt 100 200 850 C 328 1562 F Pt1...

Page 7: ...9 13 o3F Out 3 function Available When the instrument has out 3 option Range nonE Output not used With this setting the status of the this output can be driven directly from serial link AL Alarm outpu...

Page 8: ...1 0 ON off off AL1 off off off AL1 ON ON ON ON 3 The instrument does not store in EEPROM the alarm status For this reason the alarm status will be lost if a power down occurs 21 AL1L For High and low...

Page 9: ...SE br Range 1 to 9999 engineering units Note For other details see 24 HAL1 parameter 32 AL2d Alarm 2 delay Available When 26 AL2t type is different form nonE Range From oFF 0 to 9999 seconds Note The...

Page 10: ...ilable always but it is a read only parameter Range from 00 00 to 99 59 HH mm 42 Hi maximum measured value Available Available when 33 Hi Lo Hi high limit but it is a read only parameter Range Enginee...

Page 11: ...a set point equal to the minimum value of the operative range e g 10 C When the temperature in the chamber is steady take note of the temperature measured by the reference system e g 9 C 3 Set 50 A L...

Page 12: ...Exceeded indication EX OUT PK HI AL1 AL2 TC10 L Output b c d e The HI lamp d is ON When a measured value a is higher then the set point b EX lamp e lights OUT lamp b turns ON and the limit output rel...

Page 13: ...onds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set the value assigned to 44 PAS2 Level 2 password Notes 1 The factory default password for configuration p...

Page 14: ...n EN584 1 DIN 43710 1977 TC Type Ranges J 50 to 1000 C 50 0 to 999 9 C 58 to 1832 F 58 0 to 999 9 F K 50 to 1370 C 50 0 to 999 9 C 58 to 2498 F 58 0 to 999 9 F S 50 to 1760 C 50 0 to 999 9 C 58 to 320...

Page 15: ...arm output Available ever Type SSR drive Isolation Not isolated Protection Output protected from short circuit Stato logico 1 12 V 20 23 mA Stato logico 0 0 5 V Auxiliary power supply for TX NOTE this...

Page 16: ...ufacturing defects or faulty materials that are found within 18 months from manufacturing date The warranty is limited to the replacement of the instrument The tampering of the instrument or an improp...

Page 17: ...ms behaviour 0 oFF to 20 0 s 1 7 bS PV input bias 100 to 100 of the input span dP 8 di A Digital Input action 0 DI1 direct 1 DI1 reverse OUT group N Param Description Range value or selection list ele...

Page 18: ...Group N Param Description Range value or selection list elements Decimal gure 26 AL2t Alarm 2 type nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Absolute band alarm with a...

Page 19: ...tion Range value or selection list elements Decimal gure 44 PAS2 Password level 2 0 oFF to 200 0 45 PAS3 Password level 3 3 to 200 0 46 di CL Display color 0 The display color is used to show the Exce...

Page 20: ...Yokogawa Electric Corporation TC10 L ENGINEERING MANUAL PAG 20...

Reviews: