Setup Procedure 
UTAdvanced Quick Setting 
(Controlling Furnace Temperature with a Motorized Valve) 

TI 04L01L01-09EN 

 
 

Foreword 

†

  The contents of this document are subject to change without prior notice as a result of improvements in performance or functionality. 

†

  Copying or reproduction by any means of all or any part of the contents of this document without permission is strictly prohibited. 

†

  Use of this document is at the users risk. 

 

 

 

 

                             

 

Technical 
Information 

This document is subject to change without notice.

TI04L01L01-09EN

2011.12.16  1st Edition (YK)

 Overview 

This is an example wiring and settings using the UTAdvanced Quick Setting function for "temperature 
control in a furnace with a motorized valve." For more details, see the user's manual. 
 

 Relevant models 

Position proportional models of the UT32A, UT35A, UT52A, and UT55A 
 

 System 

 

 

 

 

 

 

 

 

 

 

 

 Wiring 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compensating 

Thermocouple type K 

 

Opening signal 

 

Thermocouple 
type K 

Compensating lead wire 

Power 

supply

OUT 

 

 

PV 

 

Normal rotation 
Reverse 
rotation 

COM 

100% 

0% 

 

Compensating lead wire 

Power 

supply 

OUT 

 

 

PV 

 

Normal rotation 
Reverse 
rotation 

COM 

100% 

0% 

UT32A, UT52A position proportional model 

UT35A, UT55A position proportional model 