16
Jetter AG
1 Safety instructions
Instructions on EMI
The noise immunity of a system is determined by the weakest component of
the system. For this reason, correct wiring and shielding of cables is of
paramount importance.
Measures for increasing EMI in electric plants:
Attach the JC-120MC to a DIN rail to EN 60715 having got the dimensions
35 x 7.5 mm.
The DIN rail must be electrically conducting and grounded by either of the
two ways:
•
Directly:
•
Via rear panel of the electric cabinet
Also refer to Application Note 016
EMC-compatible installation of electric
cabinets
by Jetter AG.
The following instructions are excerpts from Application Note 016:
Physically separate
signal and power lines. Jetter AG recommend
spacing greater than 20 cm. Cables and lines should cross each other at
an angle of 90°.
The following line cables must be shielded:
Analog lines, data lines, motor cables coming from inverter drives (servo
output stage, frequency converter), lines between components and
interference suppressor filter, if the suppressor filter has not been placed at
the component directly.
Shield cables
at both ends
.
Unshielded wire ends of shielded cables should be as short as possible.
The entire shield,
must, in its entire perimeter,
be drawn behind the
isolation, and then be clamped under the earthed strain relief
with the
greatest possible surface area.
When male connectors are used:
Draw the shield, in its entire perimeter, under the shielding clamp of the
metallized connector housing (impedance shielding), respectively of the
EMC gland bushing, its greatest possible surface area being clamped
under a strain relief.
Only use metallized connectors, e.g. Sub-D with metallized housing. Make
sure that the strain relief is directly connected with the housing here as
well.
Noise immunity of a
system
Measures
Содержание JC-120MC
Страница 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Страница 18: ......
Страница 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Страница 160: ......
Страница 186: ......
Страница 196: ......
Страница 395: ...Jetter AG 395 JC 120MC Programming Result When initializing the JX2 system bus the adjusted baud rate values were used...
Страница 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Страница 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Страница 586: ......
Страница 604: ......
Страница 633: ......