394
Jetter AG
10 Programming
JX2 system bus - Baud rate
The user configures the baud rate of the JX2 system bus. A reduced baud rate
allows longer lines.
The value contained in the register for baud rate configuration is remanent.
Any changes become effective only after the controller JC-120MC has been
re-booted.
Register
Description
R 200002029
Baud rate of JX2 system bus
Most modules on the JX2 system bus will automatically detect the baud rate of
the controller JC-120MC. The following modules feature automatic baud rate
detection (Auto Baud Rate):
JX2-I/O modules
JX2 slave modules
JetMove 1xx, 2xx und 6xx
IP67-I/O modules LioN-S and LJX7-CSL
The baud rate setting depends on the number of modules connected to the
JX2 system bus.
JX2-I/O modules
JX2 slave modules
JetMove
JX-SIO
IP67-I/O modules
CANopen®
modules
1000
kBaud
500
kBaud
250
kBaud
125
kBaud
x
x
x
x
x
x
x
x
x
x
x
x
x
x
To set the baud rate of the JX2 system bus proceed as follows:
Step
Action
1
Adjust the baud rate of the controller in R 200002029
Baud rate
JX2 system bus
.
If ...
... then ...
... baud rate = 1,000 kBaud,
... R 200002029 := 7.
... baud rate = 500 kBaud,
... R 200002029 := 6.
... baud rate = 250 kBaud,
... R 200002029 := 5.
... baud rate = 125 kBaud,
... R 200002029 := 4.
2
Switch off the controller and all modules on the JX2 system bus.
3
Adjust the baud rate on all modules without Auto Baud Rate.
4
Switch on the controller and all modules on the JX2 system bus.
Introduction
Registers - Overview
Modules with automatic
baud rate detection
Baud rate
Changing the Baud rate
Содержание JC-120MC
Страница 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Страница 18: ......
Страница 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Страница 160: ......
Страница 186: ......
Страница 196: ......
Страница 395: ...Jetter AG 395 JC 120MC Programming Result When initializing the JX2 system bus the adjusted baud rate values were used...
Страница 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Страница 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Страница 586: ......
Страница 604: ......
Страница 633: ......