4 Mechanical and electrical installation
Number
Part
Description
1
Jack X11
Serial interface of the JC-120MC
2
Shielding
Use shielded cables both ends of which are
connected to the metallized housing of the connector.
3
Power supply
If several displays and HMIs are used, each of them
must be individually connected to the power supply.
4 ... 7
Terminals
Interfaces of displays and HMIs
The following minimum requirements apply to cable sets:
Parameter
Description
Core cross-sectional area
0.14 mm
2
Maximum cable length
100 m
Shielding
Complete shielding, no paired shielding
Cable specification