Jetter AG
565
JC-120MC
Automatic copying of controller data
Activating the AutoCopy feature
The AutoCopy function can only be executed when the controller is booting
(i.e. after startup).
You have created the command file and stored it to the respective directory.
If the entry
AutoCopyIni
is not available in the configuration file
config.ini
the
name of the command file and of the directory is set as follows:
Value
Remarks
File name
autocopy.ini
All lower case letters
Directory
/SD/
Root directory on the SD card
Since operating system version OS Neue AutoCopy-Funktion of JC-120MC
the following applies:
Die Datei
autocopy.ini
kann in einem beliebigen Unterverzeichnis des
Stammverzeichnisses
/SD/
auf der SD-Karte sein.
Instead of
autocopy.ini
, you can name the file arbitrarily.
In this case, it is prerequisite that the configuration file
config.ini
contains the
entry
config.ini
. This entry defines the directory and file name of the command
file.
To start the AutoCopy function, proceed as follows:
Step
Action
1
Switch the controller off.
2
Insert the SD card completely into the SD slot.
3
Set the mode selector to
LOAD
position.
4
Switch the controller on
5
Wait for the red LED
D1
to be lit and for the green LED
R
and the yellow
LED
SD
to flash slowly by approximately 1 Hz.
Result:
The controller executes the AutoCopy function.
6
Wait for the red LED
D1
and for the green LED
R
to flash slowly by
approximately 1 Hz.
Result:
The AutoCopy function is set.
Introduction
Prerequisites
Activating the AutoCopy
feature
Содержание JC-120MC
Страница 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Страница 18: ......
Страница 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Страница 160: ......
Страница 186: ......
Страница 196: ......
Страница 395: ...Jetter AG 395 JC 120MC Programming Result When initializing the JX2 system bus the adjusted baud rate values were used...
Страница 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Страница 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Страница 586: ......
Страница 604: ......
Страница 633: ......