52
Jetter AG
4 Mechanical and electrical installation
Number
Element
Description
4
Not connected
Do not connect these pins
Pinout of the 9-pin male Sub-D connector on the Y-cable:
Pin
Signal name
Description
1
CMODE0
Commissioning
2
CAN-L
Data signal CAN 1
3
GND
Reference potential
4
CMODE1
Commissioning
6
CAN-L_2
Data signal CAN 2
7
CAN-H
Data signal CAN 1
8
CAN-H_2
Data signal CAN 2
Pinout of the 9-pin female Sub-D connector (CAN 1) on the Y-cable:
Pin
Signal name
Description
1
CMODE0
Commissioning
2
CAN-L
Data signal CAN 1
3
GND
Reference potential
4
CMODE1
Commissioning
7
CAN-H
Data signal CAN 1
Pinout of the 9-pin female Sub-D connector (CAN 2) on the Y-cable:
Pin
Signal name
Description
1
CMODE0
Commissioning
2
CAN-L_2
Data signal CAN 2
3
GND
Reference potential
4
CMODE1
Commissioning
7
CAN-H_2
Data signal CAN 2
Male sub-D connector
Sub-D connector (CAN 1)
Sub-D connector (CAN 2)
Содержание JC-120MC
Страница 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Страница 18: ......
Страница 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Страница 160: ......
Страница 186: ......
Страница 196: ......
Страница 395: ...Jetter AG 395 JC 120MC Programming Result When initializing the JX2 system bus the adjusted baud rate values were used...
Страница 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Страница 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Страница 586: ......
Страница 604: ......
Страница 633: ......