4 Mechanical and electrical installation
Line length and baud rate of the JX2 system bus
The maximum cable length depends on the baud rate used and the number of
expansion modules connected to the bus.
Baud rate
Cable length
Stub length
Total stub length
1,000 kBaud
25 m max.
0.3 m max.
3 m
500 kBaud
100 m max.
1.0 m max.
39 m
250 kBaud
200 m max.
3.0 m max.
78 m
125 kBaud
200 m max.
-
-
When engineering the line length, follow the rules listed below:
Each non-intelligent JX2-I/O module connected to the system bus reduces
the maximum line length by 1.0 m
Each connected intelligent JX2-I/O slave module reduces the maximum
line length by 1.0 m
Each JetMove reduces the maximum line length by 1.0 m
Each connected IP67-I/O module reduces the maximum line length by
1.0 m
The baud rate setting depends on the number of modules connected to the
JX2 system bus:
JX2-I/O modules
JX2 slave modules
JetMove
JX-SIO
CANopen®
modules
1,000
kBaud
500
kBaud
250
kBaud
125
kBaud
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cable lengths
Rules for calculating the
stub length
Baud rate
Содержание JC-120MC
Страница 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Страница 18: ......
Страница 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Страница 160: ......
Страница 186: ......
Страница 196: ......
Страница 395: ...Jetter AG 395 JC 120MC Programming Result When initializing the JX2 system bus the adjusted baud rate values were used...
Страница 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Страница 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Страница 586: ......
Страница 604: ......
Страница 633: ......