450
Jetter AG
10 Programming
Addressing
The addresses which have been received via Modbus/TCP can be modified
locally in the Modbus-TCP server. For this purpose, three registers have been
provided. The basic addresses for accessing registers, inputs and outputs are
entered into these registers. Then, the address contained in the Modbus/TCP
frame specifies the address with reference to the basic address.
Register offset
The basic address for accessing registers via Modbus/TCP is entered into
R 272702.
Register properties
Value after reset
1000000
Input offset
The basic address for accessing inputs via Modbus/TCP is entered into
R 272704.
Register properties
Value after reset
100000000
Output offset
The basic address for accessing outputs via Modbus/TCP is entered into
R 272705.
Register properties
Value after reset
100000000
The Modbus/TCP server on the JetControl receives from a Modbus/TCP client
the command
read multiple registers
starting from register number 100. The
number of registers to be read is 5. Register 272702
Register Offset
contains
the value 1000000.
Hence, registers 1000100 through 1000104 will be read.
The Modbus/TCP server on the JetControl receives from a Modbus/TCP client
the command
read input discretes
specifying input number 210 and the
instruction to read this input. Register 272704
Input Offset
contains the value
100000000.
Hence, input 100000210 of a peripheral module JX3-DI16 will be read.
Introduction
R 272702
R 272704
R 272705
Example 1
Example 2
Содержание JC-120MC
Страница 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Страница 18: ......
Страница 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Страница 160: ......
Страница 186: ......
Страница 196: ......
Страница 395: ...Jetter AG 395 JC 120MC Programming Result When initializing the JX2 system bus the adjusted baud rate values were used...
Страница 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Страница 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Страница 586: ......
Страница 604: ......
Страница 633: ......