Mechanical and electrical installation
Limitation depending on the power consumption of the modules
JX3 modules of a JX3 station are supplied with logic voltage either by a
JC-120MC controller, or a JX3-BN-xxx bus node, or a JX3-PS1 power supply
module. Each of these modules is able to supply up to 8 downstream
JX3 modules with logic voltage.
Certain JX3 modules, however, have a higher power consumption which may
reduce the number of JX3 modules that can be connected to one JX3 station.
Depending on the power consumption, you must equip the JX3 station with
additional power supply modules JX3-PS1.
The following table shows the allowed power consumption of JX3 modules
connected to the right (downstream) of the power supply module.
Power Supply Module Power consumption P
24 V
Power consumption P
5 V
JC-120MC
18 W
6 W
JX3-BN-ETH
18 W
6 W
JX3-BN-CAN
22 W
6 W
JX3-PS1
24 W
6 W
The following devices are not taken into account when calculating power
consumption:
Controller JC-120MC
Bus node JX3-BN-ETH
Bus node JX3-BN-CAN
Power supply module JX3-PS1
Introduction
Allowed power
consumption
Devices not to be taken
into account
Содержание JC-120MC
Страница 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Страница 18: ......
Страница 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Страница 160: ......
Страница 186: ......
Страница 196: ......
Страница 395: ...Jetter AG 395 JC 120MC Programming Result When initializing the JX2 system bus the adjusted baud rate values were used...
Страница 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Страница 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Страница 586: ......
Страница 604: ......
Страница 633: ......