![Jetter JC-120MC Скачать руководство пользователя страница 532](http://html1.mh-extra.com/html/jetter/jc-120mc/jc-120mc_user-manual_3870525532.webp)
532
Jetter AG
10 Programming
The structure of the
Manufacturer Hardware Version object
is shown in the
following table.
Index
Subindex
Default
Description
0x1009 0
OS version of the device
The structure of the
Manufacturer Software Version object
is shown in the
following table.
Index
Subindex
Default
Description
0x100A 0
Software version of the application
program that runs on the device
The entry in this index is made via the parameter
SWVersion
of the STX
function
CanOpenInit()
.
The structure of the
Node ID object
is shown in the following table.
Index
Subindex
Default
Description
0x100B 0
Node ID of the given device
The structure of the
Producer Heartbeat Time object
is shown in the
following table.
Index
Subindex
Default
Description
0x1017 0
1,000 [ms]
Heartbeat time
The table below lists the device registers associated with the CANopen®
Object Dictionary.
The letter x in the register number represents the CAN bus number ranging
from 0 ... CANMAX.
Register
number
Description
Value range
Attributes
Data type
40x000
Own node ID
1 ... 127
rw (read &
write)
Int
40x001
Own heartbeat
status
0 = Bootup
4 = Stopped
5 = Operational
127 =
Preoperational
255 = Offline
ro (read
only)
Int
40x002
Refer to object
0x1001
ro
Int
40x019
ro
Int (IP
format)
Manufacturer Hardware
Version object (index
0x1009)
Manufacturer Software
Version object (index
0x100A)
Node ID object (index
0x100B)
Producer Heartbeat Time
object (index 0x1017)
CANopen® registers
Содержание JC-120MC
Страница 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Страница 18: ......
Страница 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Страница 160: ......
Страница 186: ......
Страница 196: ......
Страница 395: ...Jetter AG 395 JC 120MC Programming Result When initializing the JX2 system bus the adjusted baud rate values were used...
Страница 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Страница 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Страница 586: ......
Страница 604: ......
Страница 633: ......