HD2 IP55 High-ingress Protection Series
Function parameter list
-163-
Function
code
Name
Description
Default
value Modify
P08.36
Detection value
for frequency
arrival
When the output frequency is within the
positive /negative detection range of the set
frequency, the multi-function digital output
terminal outputs "frequency arrival" signal as
shown below.
Output frequency
Set
Detection amplitude
frequency
Time t
Y,
RO1, RO2
Time t
Setting range: 0.00Hz–
(max. output
frequency)
0.00Hz
○
P08.37
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
1
○
P08.38
Energy-
consumption
brake threshold
voltage
Set the starting bus voltage of energy-
consumption brake, adjust this value properly
can brake the load effectively. The default
value will change with the change of voltage
class.
Setting range: 200.0–2000.0V
220V
voltage:
380.0V;
380V
voltage:
700.0V;
○
P08.39 Running mode
of cooling fan
0: Common running mode
1: The fan keeps running after power up
2. Running mode 2
0
○
P08.40 PWM selection
0x0000–0x1121
Ones place: PWM mode selection
0: PWM mode 1, 3PH modulation and 2PH
modulation
1: PWM mode 2, 3PH modulation
Tens place: PWM low-speed carrier limit
0: Low-speed carrier limit mode 1
1: Low-speed carrier limit mode 2
2: No limit
100’s place: Deadzone compensation method
0: Compensation method 1
1: Compensation method 2
1000’s place: PWM loading mode
0x1101
◎
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......