HD2 IP55 High-ingress Protection Series
Basic Operation Instructions
-75-
Function
code
Name
Description
Default
value
8: Set via Modbus communication
9:
Set
via
PROFIBUS/CANopen/DeviceNet
communication
10: Set via Ethernet communication
11: Set via high-speed pulse HDIB
12: Set via pulse string AB
13: Set via EtherCAT/PROFINET
communication
14: Set via PLC card
15: Reserved
P00.08
Reference object of B
frequency command
0: Max. output frequency
1: A frequency command
0
P00.09
Combination mode of setup
source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max (A, B)
5: Min (A, B)
0
P05.01–
P05.06
Function of multi-function
digital input terminal (S1–
S4, HDIA, HDIB)
10: Frequency increase (UP)
11: Frequency decrease (DOWN)
12: Clear frequency increase/decrease
setting
13: Switch-over between setup A and
setup B
14: Switch-over between combination
setup and setup A
15: Switch-over between combination
setup and setup B
/
P08.42
Reserved
/
/
P08.43
Reserved
/
/
P08.44
UP/DOWN terminal control
0x000–0x221
Ones: Frequency enabling selection
0: UP/DOWN terminal setting is valid
1: UP/DOWN terminal setting is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or
P00.07=0
1: Valid for all frequency modes
2: Invalid for multi-step speed when
multi-step speed takes priority
Hundreds: Action selection at stop
0: Valid
1: Valid during running, clear after stop
2: Valid during running, clear after
receiving stop command
0x000
P08.45
UP terminal frequency
incremental change rate 0.01–50.00 Hz/s
0.50 Hz/s
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......