HD2 IP55 High-ingress Protection Series Inverter
-74-
The HD2IP series inverter supports switch-over between different reference channels, and the
rules for channel switch-over are shown below.
Present
reference
channel
P00.09
Multi-function
terminal function 13
Channel A switches to
channel B
Multi-function
terminal function 14
Combination setup
switches to channel A
Multi-function
terminal function 15
Combination setup
switches to channel B
A
B
/
/
B
A
/
/
A+B
/
A
B
A-B
/
A
B
Max (A, B)
/
A
B
Min (A, B)
/
A
B
Note:
"/" indicates this multi-function terminal is invalid under present reference channel.
When setting the auxiliary frequency inside the inverter via multi-function terminal UP (10) and
DOWN (11), users can increase/decrease the frequency quickly by setting P08.45 (UP terminal
frequency incremental change rate) and P08.46 (DOWN terminal frequency decremental
change rate).
UP terminal
function selection=10
DOWN terminal
function selection=11
Related parameter list:
Function
code
Name
Description
Default
value
P00.03
Max. output frequency P00.04–400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05–P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz–P00.04
0.00Hz
P00.06
A frequency command
selection
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDIA
5: Set via simple PLC program
6: Set via multi-step speed running
7: Set via PID control
0
P00.07
B frequency command
selection
15
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......