HD2 IP55 High-ingress Protection Series Inverter
-214
P30.23
PID1 output
upper limit P30.24~100.0%
100.0%
○
P30.24
PID1 output
lower limit -100.0%~P30.23
0.0%
○
P30.25
Reverse
●
P30.26
PID1
deviation
input limit
0.0~100.0%
100.0%
○
P30.27
Integral
separation
threshold
0.0~200.0%
200.0%
○
P30.28
Differential
filtering
times
0~30
2
○
P30.29
PID1 output
gain
0.30~3.00
1.00
○
P30.30
PID1 output
filter time
0.000~60.000s
0.000s
○
P30.31
Feedback
upper limit
detection
value
-100.0%~100.0%
100.0% does not detect the feedback
upper limit exceeded
100.0%
○
P30.32
Feedback
lower limit
detection
value
-100.0%~100.0%
0.0% does not detect the feedback lower
limit exceeded
0.0%
○
P30.33
Feedback
exceeds
detection
time
0.0~3600.0s
1.0s
○
P30.34
PID1 control
mode
0: Differential priority processing for
feedback
1: Differential priority processing for
deviations
0
◎