HD2 IP55 High-ingress Protection Series Inverter
-84-
Set
value
Function
Description
cases of large-inertia load and free stop time; its
definition is the same with P01.08, and it is mainly used
in remote control.
7
Fault reset
External fault reset function, its function is the same
with the STOP/RST key on the keypad. This function
can be used in remote fault reset.
8
Running pause
The inverter decelerates to stop, however, all the
running parameters are in memory state, eg PLC
parameter, wobbling frequency, and PID parameter.
After this signal disappears, the inverter will revert to
the state
before stop.
9
External fault input
When external fault signal is transmitted to the inverter,
the
inverter releases fault alarm and stops.
10
Frequency increase (UP) Used to change the frequency-increase/decrease
command when the frequency is given by external
terminals.
K1
UP terminal
K2
DOWN terminal
K3
UP/DOWM
Zeroing terminal
COM
The terminal used to clear frequency-increase/decrease
setting can clear the frequency value of auxiliary
channel set by UP/DOWN, thus restoring the reference
frequency to the frequency given by main reference
frequency command channel.
11
Frequency decrease
(DOWN)
12
Clear frequency
increase/decrease setting
13 Switching between A setting
and B setting
This function is used to switch between the frequency
setting channels.
A frequency reference channel and B frequency
reference channel can be switched by no. 13 function;
the combination channel set by P00.09 and the A
frequency reference channel can be switched by no. 14
function; the combination channel set by P00.09 and the
B frequency reference channel can be switched by
no. 15 function.
14
Switching between
combination setting and A
setting
15
Switching between
combination setting and B
setting
16
Multi-step speed terminal 1 16-step speeds can be set by combining digital states
of these four terminals.
17
Multi-step speed terminal 2
18
Multi-step speed terminal 3
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......