HD2 IP55 High-ingress Protection Series
Basic Operation Instructions
-83-
Function
code
Name
Description
Default
value
P06.28 Corresponding HDO output
of lower limit
0.00–50.00kHz
0.0kHz
P06.29
Upper limit of HDO output P06.27–300.0%
100.0%
P06.30 Corresponding HDO output
of upper limit
0.00–50.00kHz
50.00kHz
P06.31
HDO output filter time
0.000s–10.000s
0.000s
5.5.11 Digital input
The HD2IP series inverter carries four programmable digital input terminals and two HDI input
terminals. The function of all the digital input terminals can be programmed by function codes.
HDI input terminal can be set to act as high-speed pulse input terminal or common digital input
terminal; if it is set to act as high-speed pulse input terminal, users can also set HDIA or HDIB
high-speed pulse input to serve as the frequency reference and encoder signal input.
P05.08 (input terminal polarity)
P05.12
P05.09 (digital filter time)
P05.13
P05.15
P05.17
P05.19
P05.21
P05.23
Digital function selection
Run
This parameter is used to set the corresponding function of digital multi-function input
terminals.
Note:
Two different multi-function input terminals cannot be set to the same function.
Set
value
Function
Description
0
No function
The inverter does not act even if there is signal input;
users can set the unused terminals to "no function" to
avoid misacts.
1
Forward running (FWD) Control the forward/reverse running of the inverter by
external terminals.
2
Reverse running (REV)
3
3-wire control
Set the inverter running mode to the 3-wire control
mode by this terminal. See P05.13 for details.
4
Forward jogging
Frequency when jogging, see P08.06, P08.07 and
P08.08 for jogging acceleration/deceleration time.
5
Reverse jogging
6
Coast to stop
The inverter blocks output, and the stop process of
motor is uncontrolled by the inverter. This mode is
applied in
T delay
P05.14
T delay
P05.16
T delay
P05.18
T delay
P05.20
T delay
P05.22
T delay
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......