HD2 IP55 High-ingress Protection Series Inverter
Function parameter list
-219-
automatically, if the PID output is
negative, the feedback is less than
P31.27 and continues P31.28 time, PID2
stop automatically
P31.28
PID2 stop
delay time 0.0~300.0s
1.0s
○
P31.29
PID2 enable
selection
0
:
PID2 disable.
1
:
PID2 enable
0
○
P32 group Fire override mode group
P32.00
Fire mode
functions
0: Disable.
1: Fire mode 1
2: Fire mode 2
Fire mode 1, when a fire occurs, inverter
runs consistently until damage.
Fire mode 2, inverter runs consistently
until display fault OUT1/OUT2/ OUT3/
OC1/OC2/OC3/OV1/OV2/OV3.
0
◎
P32.01
Fire mode
running
frequency
0.00Hz~P00.03
50.00H
z
○
P32.02
Fire mode
flag
0
:
Not enter fire mode.
1
:
If enter fire mode, after 5 minutes,
P32.02 change to 1 automatically,
inverter warranty is invalid.
0
●
P33 HVAC Group
P33.00
HVAC
function
0
:
Invalid
1
:
Valid
0: HVAC function is invalid; all pump
control logic is invalid.
1: inverter enables HVAC function, be
suitable for water supply application.
1
◎
P33.01
Hibernation
type
0: Run with lower limit frequency.
1: Hibernation according to running
frequency.
2: Hibernation according to deviation
P33.01=1, Hibernation according to
1
○
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......