P01.19
Action
selection
when the
running
frequency is
below lower
limit (lower
limit should
be larger than
0)
This function code is used to set the running
state of VFD when the set frequency is below
lower limit frequency.
0: Run in lower limit of the frequency
1: Stop
2: Sleep
When the set frequency is below lower limit
frequency, the VFD coasts to stop; when the set
frequency is above lower limit again and
continues to be so after the time set by P01.20
elapses, the VFD will be restored to running
state automatically.
0
◎
P01.20
Wake-up-fro
m-sleep delay
This function code is used to set the sleep delay.
When the running frequency of VFD is below the
lower limit frequency, the VFD enters sleep
state; when the set frequency is above the lower
limit again and continues to be so after the time
set by
P01.20
elapses, the VFD will run
automatically.
Sleep
Set frequency curve:
Running frequency cur ve:
t1 < P01.20, the VFD does not run
t0=P01.34, sleep delay
Run
t2
t1
Run
t0
Frequency lower
limit f0
Frequency f
Time t
stop
Coast to
t1+t2
≥
P01.20, the VFD runs
Setting range: 0.0
–3600.0s (valid when
P01.19
is 2)
0.0s
○
P01.21
Restart after
power cut
This function code sets the automatic running of
the VFD at next power-on after power down.
0: Disabled restart
1: Enable restart, namely the VFD will run
automatically after the time set by
P01.22
elapses if the starting conditions are met.
0
○
P01.22
Waiting time
of restart after
power cut
This function code sets the waiting time before
automatically running at next power-on after
power down.
1.0s
○
Function parameter list
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......