HD2 IP55 High-ingress Protection Series Inverter
-272
2005H Setting of the upper limit of the forward running
frequency (0–Fmax, unit: 0.01 Hz)
R/W
2006H
Setting of the upper limit of the reverse running
frequency (0–Fmax, unit: 0.01 Hz)
R/W
2007H
Upper limit of the electromechanical torque (0–
3000, 1000 corresponding to 100.0% of the
rated
current of the inverter)
R/W
2008H
Upper limit of the brake torque (0–3000, 1000
corresponding to 100.0% of the rated current of
the motor)
R/W
2009H
Special control command word:
Bit1–0: =00: Motor 1 =01: Motor 2
=10: Motor 3
=11: Motor 4
Bit2: =1 Torque control disabled =0: Torque
control cannot be disabled
Bit3: =1 Power consumption reset to 0
=0: Power consumption not reset
Bit4: =1 Pre-excitation
=0: Pre-
excitation disabled
Bit5: =1 DC brake =0: DC brake disabled
R/W
200AH
Virtual input terminal command, range: 0x000–
0x3FF
Corresponding to S8/S7/S6/S5/HDIB/HDIA/S4/
S3/ S2/S1
R/W
200BH
Virtual output terminal command, range: 0x00–
0x0F
Corresponding to local RO2/RO1/HDO/Y1
R/W
200CH
Voltage setting (used when V/F separation is
implemented)
(0–1000, 1000 corresponding to 100.0% of the
rated voltage of the motor)
R/W
200DH
AO output setting 1 (-1000–+1000, 1000
corresponding to 100.0%)
R/W
200EH
AO output setting 2 (-1000–+1000, 1000
corresponding to 100.0%)
R/W
0001H: Forward running
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......