HD2 IP55 High-ingress Protection Series Inverter
Function parameter list
-221-
Hibernation
Hibernation status
Difference between PID1
reference and feedback value
≥
P33.08 wake up deviation
Status hold time reach
P33.09 wake up delay time
Wake up
Hibernation
Y
N
N
Y
If DI hibernation trigger
signal is valid
Hibernation
If DI wake up trigger signal
is valid
Wake up
N
N
Y
Y
P33.08
Hibernation
wake up.
deviation
0.0~30.0% (relative to Max. PID1)
If PID is positive, allow waking up only
when feedback is smaller than reference,
the absolute value of the actual deviation
is larger than P33.08 value and the hold
time is larger than P33.09.
If PID is negative, allow waking up only
when feedback is bigger than reference,
the absolute value of the actual deviation
is larger than P33.08 value and the hold
time is larger than P33.09.
2.0%
○
P33.09
Hibernation
wake up.
delay time
0.0~3600.0s
2.0s
○