HD2 IP55 High-ingress Protection Series Inverter
-128
Function
code
Name
Description
Default
value Modify
coefficient of
motor 1
current, K is motor overload protection
coefficient.
The smaller the K, the larger the value of M,
and the easier the protection.
When M=116%, protection is performed after
motor overload lasts for 1 hour; when
M=150%, protection is performed after motor
overload lasts for 12 minutes; when M=180%,
protection is performed after motor overload
lasts for 5 minutes; when M=200%, protection
is performed after motor overload lasts for 60
seconds; and when
M≥400%,
protection is
performed immediately.
Setting range: 20.0%–120.0%
P02.28
Power display
calibration
coefficient of
motor 1
This function adjusts the power display value
of motor 1 only, and it does not affect the
control performance of the inverter.
Setting range: 0.00–3.00
1.00
○
P02.29
Parameter
display of motor
1
0: Display as per motor type; under this mode,
only parameters related to current motor type
will be displayed.
1: Display all; under this mode, all the motor
parameters will be displayed.
0
○
P02.30 System inertia
of motor 1
0–30.000kgm2
0
○
P02.31–
P02.32
Reserved
/
/
/
P03 group––Vector control of motor 1
Function
code
Name
Description
Default
value Modify
P03.00
Speed loop
proportional gain
1
fit for vector
, speed loop
; above
20.0
○
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......