HD2 IP55 High-ingress Protection Series Inverter
-250
过电流
7.6.7 Motor stalls during ACC
Whether the ACC
time is too short?
Yes
No
Check the voltage of the
terminals of the motor with a
multimeter. Whether the voltage
is within the defined range?
Yes
No
Whether the load
or inertia is too
large?
No
Yes
Whether a special
motor is used?
Yes
No
Yes
Whether the load
torque is too large?
No
No Whether the
torque boost
is too high?
Yes
Whether it is V/F
control?
Yes
No
Whether parameter
autotuning is
performed?
Yes
No
Motor stalls during
ACC
If it is an inverter fault or
interference, contact our
company
Overcurrent
Modify the torque
boost
If it is a inverter fault
or interference,
contact our company
Reduce the inertia of
the load and
increase the capacity
of the inverter
Reduce the torque of
the load and
increase the capacity
of the inverter
Contact our
company
Use larger cables, shorten the
wiring distance, adjust the voltage
drop of the output reactor, etc.
Increase the ACC
time
Содержание HD2 IP Series