HD2 IP55 High-ingress Protection Series Inverter
-248
7.6.5 Unusual heating of motor
Whether the motor
parameters are set
correctly?
Yes
No
Whether parameter
autotuning is
performed?
Yes
No
No
Whether the inverter runs
at a low speed all the
time?
Whether it is a variable-
frequency motor?
Yes
No
Whether the load is
too heavy?
No
Whether the three
phases of the motor are
balanced?
Yes
Yes
No
Whether the carrier
frequency is too low?
No
Yes
Whether the motor
cable is too long?
No
Yes
Unusual heating of the
motor
If it is an inverter fault,
contact our company
Add an output
filter
Set the carrier
frequency
properly
Replace the
motor
Reduce the
load
Use a variable-
frequency motor
Parameter
autotune
Set the motor
parameters
correctly