HD2 IP55 High-ingress Protection Series
Basic Operation Instructions
-70-
3. Logic diagram for restart after automatic fault reset
Related parameter list:
Function
code
Name
Description
Default
value
P00.01 Running command channel
0: Keypad
1: Terminal
2: Communication
0
P00.11
Acceleration time 1
0.0–3600.0s
Depend
on model
P00.12
Deceleration time 1
0.0–3600.0s
Depend
on model
P01.00
Running mode of start
0: Direct start
1: Start after DC brake
2: Start after speed-track 1
3: Start after speed-track 2
0
P01.01 Starting frequency of direct
start
0.00–50.00Hz
0.50Hz
P01.02
Hold time of starting
frequency
0.0–50.0s
0.0s
P01.03
DC brake current before
start
0.0–100.0%
0.0%
P01.04 DC brake time before start 0.00–50.00s
0.00s
P01.05
Acceleration/deceleration
mode
0: Straight line
1: S curve
Note: If mode 1 is selected, it is required
to set P01.07, P01.27 and P01.08
accordingly,
0
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
P01.09
Starting frequency of DC
brake after stop
0.00Hz–P00.03 (max. output frequency) 0.00Hz
In running
inverter fault
Automatic reset times
N
of inverter fault<P08.28
Automatic reset
interval of
inverter
N
Display fault
code, and stop
inverter fault
reset, start
running
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......