HD2 IP55 High-ingress Protection Series Inverter
Function parameter list
-213-
P30.14
Feedback
source 2
conversion
gain
0.000~600.00s
1.00s
○
P30.15
Feedback
source
combination
selection
0
:
No combination; feedback source 1
1
:
Sum; feedback source 1 + feedback
source 2
2
:
Difference; feedback source 1 -
feedback source 2
3: Average; average of feedback source
1 and feedback source 2
4
:
Min; Min (feedback source 1,
feedback source 2)
5: Max; Max (feedback source 1,
feedback source 2)
2
○
P30.16
PID1 polarity
selection
0: Positive polarity
1: Negative polarity
0
○
P30.17
PID1
Proportional
gain (Kp)
0.00~100.00
1.00
○
P30.18
PID1 Integral
time (Ti)
0.00~30.00s
0.10s
○
P30.19
PID1
Derivative
time (Td)
0.00~10.00s
0.00s
○
P30.20
PID1
Sampling
cycle(T)
0.001~10.000s
This means the sampling cycle of
feedback. The regulator operates once
during each sampling cycle.
The larger the sampling cycle, the slower
the response.
0.100s
○
P30.21
PID1 control
dead zone 0.0~100.0%
1.0%
○
P30.22
PID1 dead
zone delay
time
0.0~300.0s
PID deviation less than P30.21, and keep
status time P30.22, PID enter dead zone,
PID adjustment is not performed.
1.0s
○
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......