HD2 IP55 High-ingress Protection Series Inverter
-100
Response
After adjustment
Related parameter list:
Function
code
Name
Description
Default
value
P09.00
PID reference source
0: Keypad (P09.01)
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Multi-step
6: Modbus communication
7:
PROFIBUS/CANopen/DeviceNet
communication
8: Ethernet communication
9: High-speed pulse HDIB
10:
EtherCAT/PROFINET
communication
11: Programmable extension card
12: Reserved
0
P09.01
Pre-set PID reference of
keypad
-100.0%–100.0%
0.0%
P09.02
PID feedback source
0: AI1
1: AI2
2: AI3
3: High-speed pulse HDIA
4: Modbus communication
5:
PROFIBUS/CANopen/DeviceNet
communication
6: Ethernet communication
7: High-speed pulse HDIB
8: EtherCAT/PROFINET communication
9: Programmable extension card
10: Reserved
0
P09.03
PID output characteristics 0: PID output is positive characteristic
1: PID output is negative characteristic
0
P09.04
Proportional gain (Kp) 0.00–100.00
1.80
Before
adjustment
Time t
Basic Operation Instructions