HD2 IP55 High-ingress Protection Series Inverters
Basic Operation Instructions
-49-
Function
code
Name
Description
Default
value
P00.18
Function parameter
restoration
0: No operation
1: Restore to default value
2: Clear fault history
Note:
After the selected function operations
are done, this function code will be restored
to 0 automatically. Restoration to default
value will clear the user password. Exercise
in caution.
0
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.01
Rated power of
asynchronous motor 1 0.1–3000.0kW
Depend
on model
P02.02
Rated frequency of
asynchronous motor 1 0.01Hz–P00.03 (max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous motor 1 1–60000rpm
Depend
on model
P02.04
Rated voltage of
asynchronous motor 1 0–1200V
Depend
on model
P02.05
Rated current of
asynchronous motor 1 0.8–6000.0A
Depend
on model
P02.15
Rated power of
synchronous motor 1 0.1–3000.0kW
Depend
on model
P02.16
Rated frequency of
synchronous motor 1 0.01Hz–P00.03 (max. output frequency)
50.00Hz
P02.17 Number of pole pairs of
synchronous motor 1 1–50
2
P02.18
Rated voltage of
synchronous motor 1 0–1200V
Depend
on model
P02.19
Rated current of
synchronous motor 1 0.8–6000.0A
Depend
on model
P05.01–
P05.06
Function of
multi-function digital
input terminal (S1–S4,
HDIA, HDIB)
36: Command switches to keypad
37: Command switches to terminal
38: Command switches to communication
/
P07.01
Reserved
/
/
P07.02
QUICK/JOG key
function
Range: 0x00–0x27
Ones: QUICK/JOG key function selection
0: No function
1: Jogging
2: Reserved
3: Switching between
f o r w a r d /reverse rotation
4: Clear UP/DOWN setting
5: Coast to stop
6: Switch running command reference mode
by sequence
7: Reserved
Tens: Reserved
0x01
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...