HD2 IP55 High-ingress Protection Series Inverter
-130
Function
code
Name
Description
Default
value Modify
P03.09
Current loop
proportional
coefficient P
Note:
1. These two parameters are used to adjust
PI parameters of current loop; it affects
dynamic response speed and control
precision of the system directly. The default
value needs no adjustment under common
conditions;
2. Fit for SVC mode 0 (
=0) , SVC
mode 1 (P00.00=1) and VC mode (
=3);
Setting range: 0–65535
1000
○
P03.10
Current loop
integral
coefficient I
1000
○
P03.11 Torque setup
mode selection
1: Keypad (P03.12)
2: AI1
3: AI2
4: AI3
5: Pulse frequency HDIA
6: Multi-step torque
7: Modbus communication
8:
PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: Pulse frequency HDIB
11: EtherCAT/PROFINET communication
12: PLC
Note:
For setting sources 2–6 and 10, 100%
corresponds to three times the rated motor
current.
0
○
P03.12 Torque set by
keypad
-300.0%–300.0% (rated motor current)
20.0%
○
P03.13
Torque
reference filter
time
0.000–10.000s
0.010s
○
P03.14
Source of upper
limit frequency
setup of forward
rotation in
torque control
0: Keypad (
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Multi-step
6: Modbus communication
7:
PROFIBUS/CANopen/DeviceNet
communication
8: Ethernet communication
9: Pulse frequency HDIB
10: EtherCAT/PROFINET communication
11: PLC
12: Reserved
Note:
For setting sources 1–9, 100%
corresponds to the max. frequency.
0
○
Function parameter list
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......