HD2 IP55 High-ingress Protection Series Inverter
-138
Function
Name
Description
Default
Modify
code
value
Oscillation
P04.25
control
threshold of 0.00Hz–
(max. output frequency)
30.00Hz
○
motor 2
0: No action
P04.26 Energy-saving
run
1: Automatic energy-saving operation
Under light-load state, the motor can adjust
the output voltage automatically to achieve
0
◎
energy-saving purpose
0: Keypad; output voltage is determined by
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step (the set value is determined by
P04.27
Channel of
voltage setup
P10 group)
6: PID
7: Modbus communication
0
○
8:
PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: HDIB
11: EtherCAT/PROFINET communication
12: PLC programmable card
13: Reserved
P04.28
Set voltage
value via
keypad
When the channel for voltage setup is set to
"keypad", the value of this function code is
digital voltage set value.
Setting range: 0.0%–100.0%
100.0%
○
P04.29
Voltage
acceleration
time
Voltage increase time means the time needed
from outputting the min. voltage to
accelerating to output the max. voltage.
5.0s
○
P04.30
Voltage
deceleration
time
Voltage decrease time means the time
needed from outputting max. voltage to
outputting the min. voltage
Setting range: 0.0–3600.0s
5.0s
○
P04.31
Max. output Set the upper/lower limit value of output
100.0%
◎
voltage
voltage.
P04.32
Min. output
voltage
V set
t2=P04.30
t2
Time t
0.0%
◎
Vmin
t1
Function parameter list
Содержание HD2 IP Series
Страница 1: ......
Страница 16: ......
Страница 40: ......
Страница 107: ......
Страница 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Страница 213: ......
Страница 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Страница 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Страница 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Страница 361: ......