2-21
,
(GCU internal failure or inverter unit internal failure)
E-06
E-05
Check the generator (P. 11-7).
Replace the stator (P. 11-5).
Normal
Check the main wire harness in the control box for open or
short circuit and for proper connection.
Replace or repair the main wire
harness.
Abnormal
Normal
Check the harness connecting the generator and GCU for open
or short circuit and for proper connection.
Replace or repair the control wire
harness and/or generator wire
harness.
Abnormal
Normal
Check the inverter unit (P. 6-3 and 4).
Replace the inverter unit (P. 6-2).
Abnormal
Normal
Turn the ignition switch OFF and then restart the engine and
check the error code. If the same error occurs, replace the GCU
(P. 6-6).
Abnormal
GCU
Bu
W
Viewed from terminal side
GENERATOR
(SLAVE)
GENERATOR WIRE
HARNESS
CONTROL WIRE
HARNESS
Bu: BLUE
R: RED
W: WHITE
Wire harness check points
R
Bu
W
R