Firmware V3.13
21.04.2021
65/466
•
•
•
•
•
5.7.19 Emergency Op.
In the event of a failure of the temperature measurement, i.e. the superheat regulation, refrigeration continues
to operate at an emergency opening degree. This emergency opening degree is calculated from the average
value of the opening degree of the last day (24 hours) and has an upper limit defined by a configurable
parameter.
Parameter Not-Öffnungsgrad
An upper limit for the emergency opening degree is set via the parameter
Max. Not-Öffnungsgrad
(menu
6-2-7).
The parameter
Max. Not-Öffnungsgrad
also applies when it has not been possible to calculate a 24 hour
value for the opening degree, for example following a first start.
Failure of case and room temperature control
If both sensors for case and room temperature control fail, the emergency opening degree is used for
further control. The superheat controller remains active and can reduce the emergency opening degree
limit.
Failure of the superheat control
If the superheat control fails, the system switches to emergency operation and outputs the emergency
opening degree. The temperature controller remains active and can also reduce the emergency opening
degree limit.
Failure of case and room temperature control and superheat control
The emergency opening degree is output
ATTENTION
Compressor damage!
Danger from liquid refrigerant on the suction side of the compressor!
The issued emergency
opening degree may be too high for the current operating point as the superheat controller is not
active. Therefore, there is the risk of flooding of the evaporator! Emergency operation should therefore
only be active for a short bridging period.
In the event of failure of one of the two sensors, regulation is performed with the remaining sensor
without switching to emergency operation.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...