Firmware V3.13
21.04.2021
138/466
12.
Select menu
2 Setpoints - 1 Cooling - Zone 1 / Zone 2 / Zone 1U / Zone 2U
.
2 Setpoints - 1 Cooling - Zone 1 - 2 - Um1 - Um2
KÜHLUNG x POS: XXX
...
Überhitzung XK
Superheat setpoint of the superheat controller
Min. Überh.XK
If the minimum superheat is undercut, the controller closes the associated E-
vale and sets the I-sum (NOT: I-component) to 0 if the parameter
Reset I-
Summ
is set to ON.
Zweipunktreg. AUS
The temperature control no longer operates continuously but as on-off
controller. This is used for enable / disable of the superheat control (TEV
emulation).
MOP-Punkt XX°C
A value not equal to "–" must be set here if the MOP function is required. If t0
exceeds this value, the opening degree is reduced as t0 rises.
13.
Return to the main menu of the store computer / operator terminal by tapping the
ESC
button multiple
times.
14.
Select the menu
7 Monitoring - 3 Configuration
in the main menu of the store computer / operator
terminal and input, among other things, the node name of the case controller in plain text.
7 Monitoring - 3 Configuration
KONFIGURATION Kn.nnn
Input of the CAN bus address: Select the case controller with the corresponding
CAN bus address (node No. = 1..99) to be parametrised using the cursor or by
direct input.
Teilnehmername
Input node name (e.g. Cheese Counter)
Position XXXXX
Input of the position of the node in the store
Priorität X
Input of the desired priority
15. Ending basic configuration of the controller
Tap the
ESC
button multiple times to return to the main menu. This ends the basic configuration of the
controller.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...