Firmware V3.13
21.04.2021
377/466
•
Menu 6-2-6 Analog inputs
ANALOG INPUTS POS: XXXXX
Entry
Default
AIN1 activ x
Analogue input Z1 use (=Y)
do not use (=N)
(Y,N)
N
Refrig.Z 1 xxxx
Selection of refrigerant zone 1
None
R404a ..
R438A*
None
LP Z1 Min xxx bar
Smallest pressure value for pressure monitoring
at 4mA
0.0 .. 2.0 bar
0.0 bar
LP Z1 Max xxx bar
Largest pressure value for pressure monitoring
at 20 mA
8.0 .. 200.0 bar
10.0 bar
AIN1 Send CAN
This parameter is used to instruct the case
controller to make the local t0 (AIN1) available via
CAN bus.
ONLY possible when the parameter AIN1 active = Y
(Y,N)
N
AIN1 Rcv. CAN xx
CAN bus address of the remote case controller
from which the t
0
is received.
1..99
--
AIN1 Rcv. Inp x
This parameter is used to specify the zone from
which the t0 is taken.
(refers to the parameter
AIN1 Rcv. Inp
)
1,2
1
AIN2 activ x
Analogue input Z2 use (=Y)
do not use (=N)
(Y,N)
N
Refrig.Z 2 xxxx
Selection of refrigerant zone 2
None
R404a ..
R438A*
None
Fct. AIN2 xxxxx
Function of the analogue input zone 2
t0Z2 For recording only
t0Z2ctl For regulation
t0Z2,
toZ2ctl,
Humidity, tc
HP Z2 Min xxx bar
Smallest pressure value for pressure monitoring
at 4mA
0.0 .. 2.0 bar
0.0 bar
HP Z2 Max xxx bar
Largest pressure value for pressure monitoring
at 20 mA
8.0 .. 200.0 bar
10.0 bar
AIN2 Send CAN
This parameter is used to instruct the case
controller to make the locally measured value of
analogue input 2 (AIN2) available via CAN bus.
ONLY possible when the parameter AIN2 active = Y
(Y,N)
N
AIN2 Rcv. CAN xx
CAN bus address of the remote case controller
which provides the locally measured analogue
value.
1..99
--
AIN2 Rcv. Inp x
This parameter is used to specify the zone from
which the locally measured analogue value is
taken.
(refers to the parameter
AIN2 Rcv. Inp
)
1,2
2
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...