12 Technical Data of UA 4xx E
12.1 Electrical data
UA 400 E CC / UA 401 E CC / UA 410 E AC
Electrical data
Operating voltage
230 V AC (+/- 10%), 50/60 Hz (+/- 3 Hz)
Rated power
11 VA
Leakage current via PE
max 1 mA
Relay outputs
4 x normally open contact, 230 V AC, floating output, min 10 mA
Load type: ohmic: max. 6 A inductive: max. 3 A, cos phi = 0.4
1 x changeover contact, 230 V AC, floating output, min 10 mA (UA 401 E: without
changeover)
Load type: ohmic: max. 6 A inductive: max. 3 A, cos phi = 0.4
Semiconductor relay (SSR = Solid State Relay, normally open contact)
:
2 x 250 V AC (UA 401 E: only 1), 1 A, must be externally fused with 1.25 A
superflink (FF), rated voltage 250 V AC, with melting integral << 10.4 A
2
s and
tripping time at 8.0 A < 10 ms, (e.g. part number 70 001 40 - manufacturer SIBA).
Note
: If large inductive loads (e.g. coils of valves) should be switched via the
semiconductor relays (relays 2/3), protective devices appropriate to the loads must
be connected (e.g. an RC element and a varistor) in order to prevent the
destruction of the SSRs due to overvoltage. Information about appropriate
protective devices as well as measures for the minimisation of overvoltage can be
obtained from the manufacturer.
Transistor outputs
2 x 24 V DC pull down switching transistor with internal current limitation to 50 mA
for lighting control and frame heater
Digital inputs
4 x 230 V AC, floating output
Analogue inputs
1)
10 x 2-wire temperature sensor for sensor types L243/K243, K277, 5K3A1 (UA
401 E: only 5)
Note
: If sensor cables are exclusively laid within the refrigerated case to be
monitored and sources of interference (e.g. from parallel power cables) are not
anticipated, then it is possible to dispense with shielding.
Only UA 410 E AC:
2 x 4..20 mA
Analogue outputs
1)
Only UA 410 E AC:
2 x 0..10 V short-circuit protection
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
Overvoltage category III (test voltage 4.0 kV) / contamination degree 2:
All connections of the
device provided for operation with 230 V AC supply voltage
must
be wired with the same phase
conductor. 400 V AC between neighbouring connection terminals is
not
permitted!
Overvoltage category II (test voltage 2.5 kV) / contamination degree 2
or
overvoltage category II (test voltage 2.5 kV) / contamination degree 1:
Different phase conductors
may be used. 400 V AC between neighbouring connection terminals is permitted
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...