Menu 3-2-a Def.Tim.Z2
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Setting for how temperature zone 2 should
defrost:
- MitZ1 Together with zone 1
- INT Internally
- EXT Externally – the defrost of both
temperature
zones is started simultaneously via the external
signal
↑, ↓,
(ViaZ1(ViaZ1,EXT,
INT)
ViatZ1
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
↑, ↓,
(ON/OFF)
OFF
Defr. 1 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day; shown only when paramter
defrost
timer
= INT
↑, ↓,
(Mo-Su) or numbers (hh:mm)
Mo-Su
01:00
...
Defr. 14 xxxxx hh:mm
Menu 3-3 Toggle Setpoints
TOGGLE POS: XXXXX
Entry
Default
Status XXX
Setpoint toggle for alternative set of setpoints
(setpoint set toggle)
Toggle Setp. XXX
Setpoint toggle via
- EXT digital input D21/22
- INT internal timer
- CAN CAN bus
- „--“ deactivated
↑, ↓,
(EXT, INT,
CAN, --)
EXT
Toggle interv. X m
The interval for the cyclical toggling between
standard and alternative setpoint data records; only
appears when the internal setpoint toggling is
activated (menu 3-3).
--, 10..60
-- min
Alt ON: xxxxx hh:mm
Start time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu
3-3)
↑, ↓,
(Mo-Su) or numbers (hh:mm)
Mo-Su
21:00
AltOFF: xxxxx hh:mm
End time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu
3-3)
Mo-Su
05:00
Alt ON: xxxxx hh:mm
Start time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu
3-3)
↑, ↓
(Mo-Su) or numbers (hh:mm)
Su
05:00
AltOFF: xxxxx hh:mm
End time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu
3-3)
Su
21:00
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...