Firmware V3.13
21.04.2021
295/466
•
1.
2.
3.
4.
Menu 6-2-4 230V Inputs
230V INPUT POS: XXXXX
Entry
Default
Entry1: XXXXXXXXXX
Function of digital input 1 D11/D12
1)
ABTAUUHR
Entry2: XXXXXXXXXX
Function of digital input 2 D21/D22
2)
TOGGLE SETP.
Entry3: XXXXXXXXXX
Function of digital input 3 D31/D32
3)
MANUAL OFF.
Entry4: XXXXXXXXXX
Function of digital input 4 D41/D42
4)
Extern.Alarm
XXXXXXXXXXXXXXXXXXX
Freely configurable alarm text for digital input
4, the default text is “CO
2
-Alarm”
Text
CO2-Alarm
Inv. D1 XXX
Inverting of digital input 1
↑, ↓, (ON/OFF)
OFF
Inv. D2 XXX
Inverting of digital input 2
OFF
Inv. D3 XXX
Inverting of digital input 3
OFF
Inv. D4 XXX
Inverting of digital input 4
OFF
Possible settings for the digital inputs:
DEFR.TIMER Defrost timer*
MANUAL OFF. Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
TOGGLE SETP. Toggle setpoint
TOGGLE SETP Toggle setpoint *
MANUAL OFF Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
MANUAL OFF Manual shutoff both zones *
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
EXT ALARM External Alarm *
MANUAL OFF Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
TOGGLE SETP Toggle setpoint
*Factory setting
ATTENTION
Damage to the system and stock loss!
Only trained personnel should be allowed to change digital
inputs, as chenges can affect other functions.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...