Firmware V3.13
21.04.2021
249/466
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Defrost initiation via Input D11/12 (EXT) or
internal (INT)
↑, ↓, (EXT, INT)
INT
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
↑, ↓, (ON/OFF)
OFF
Def.Tim.Z2 →
Separate defrost timer for zone 2
Menu 3-2-a
Defr. 1 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter
defrost timer
= INT
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
20:15
...
Defr. 14 xxxxx hh:mm
*) Parameter is automatically set to ON at first start for the duration of the safe defrost time.